IM Topway T2 installation and commissioning Flowmeters Nov 2013
01993 824900
PB
01993 824900
Topway T2 Manifold
Topway T2 Manifold
Flowmeter Adjustment
Topway T2 Manifold Installation and Commissioning Instructions
1
Flowmeter Adjustment
Range of measurement 0-4 l/min Maximum operating pressure 6 bars Max. operating temperature 90 °C Kv = 0.15 (1 l/min) -0.55 (4 l/min) Kv max off scale = 0.9 Precision ±10% fs fs= Bottom of scaleHow to balance the circuits using flowmeters Flowmeters have a double regulating function i.e. they -Turn the red collar anticlockwise approximately three
Combined Flow regulator and
Red Collar
Flowmeter tube
Fig. 1Fig. 2
1010010001010
01
000p [mbar]
0 Kv=0,030,5 Kv=0,031 Kv=0,031,5 Kv=0,082 Kv=0,192,5 Kv=0,333 Kv=0,493,5 Kv=0,61TA Kv=0,64
Flow rate /h
TA = Fully open. The above values refer to water temperature at 15 °C.;